Parameter
Units
Glendale Plant
Northside Plant
West Lakeland WLRF
Biochemical Oxygen Demand BOD
mg/L
2200
3000
1*
Conductivity
uS
4300
8000
4300
Arsenic
mg/L
0.105
0.045
0.105
Cadmium
MG/L
0.025
0.03
0.025
Chromium
mg/L
4.29
5.1
4.29
Copper
mg/L
0.58
1.045
0.58
Cyanide
mg/L
0.065
0.08
0.065
Lead
MG/L
0.17
0.252
0.17
Mercury
mg/L
0.005
0.006
0.005
Molybdenum
mg/L
0.28
0.045
0.28
Nickel
mg/L
0.45
0.38
0.45
Selenium
MG/L
0.08
0.045
0.08
Zinc
mg/L
0.7
0.81
0.7
Silver
mg/L
0.45
0.5
0.45
Phenol
mg/L
18
18
18
Total Oil/Grease
mg/L
450
450
450
Total Petroleum Hydrocarbons
mg/L
100
100
100
pH
S.U.
5.5< >10.5
5.5< >10.5
5.5< >10.5
* Any user discharging into the West Lakeland Waste Load Reduction Facility (WLWLRF) shall comply with the Limits established for the Glendale Plant with the exception of BOD. Any user discharging into the WLWLRF shall be allocated a portion of the BOD, in pounds per day, based on 80% of the designed capacity of the WLWLRF.