City of Lakeland Local Limits Table


Chapter 102 of the City of Lakeland Code

August 2022

  Glendale WRF   Northside WRF   West Lakeland WLRF (1)  
Parameter Chronic* TRC**   Chronic* TRC**   Chronic* TRC** Units
Arsenic 0.188 0.2256   0.485 0.582   0.188 0.2256 mg/L
Cadmium 0.014 0.0168   0.016 0.0192   0.014 0.0168 mg/L
Chromium 1.38 1.656   2.972 3.5664   1.38 1.656 mg/L
Copper 0.386 0.4632   0.566 0.6792   0.386 0.4632 mg/L
Cyanide 0.057 0.0684   0.166 0.1992   0.057 0.0684 mg/L
Lead 0.276 0.3312   0.34 0.408   0.276 0.3312 mg/L
Mercury 0.00775 0.0093   0.00344 0.004128   0.00775 0.0093 mg/L
Molybdenum 0.25 0.3   2.45 2.94   0.25 0.3 mg/L
Nickel 0.986 1.1832   2.43 2.916   0.986 1.1832 mg/L
Selenium 0.021 0.0252   0.163 0.1956   0.021 0.0252 mg/L
Zinc 0.745 0.894   1.74 2.088   0.745 0.894 mg/L
Silver 1.065 1.278   0.0076 0.00912   1.065 1.278 mg/L
BOD 2378 3329   2266 3172   2 2 mg/L
pH 5.5 - 10.5 5.5 - 10.5   5.5 - 10.5 5.5 - 10.5   5.5 - 10.5 5.5 - 10.5 SU
Conductivity 3795 4554   5634 6760   3795 4554

µS

Oil & Grease 391 547   481 673   391 547 mg/L

*Chronic values are the numerical Local Limits for the City of Lakeland.  A violation of any magnitude is a Chronic Violation.

*** TRC (Technical Review Criteria) is either 1.4 times the Local Limit for conventionals or 1.2 times the Local Limit for all other parameters.  A violation above this value is both a Chronic and a TRC violation.

(1) Local Limits for the West Lakeland WLRF are the same as the  Glendale WRF as the effluent from the WLRF goes to Glendale.

(2) The BOD limit for the WLRF shall be an allocation of the available design capacity after removing a portion for reserve for all users of the WLRF.  Each user shall be allocated a portion of this capacity in a Wastewater Discharge Permit